Fire safety in a restaurant in Poland is a set of duties that the statute and the Ministry of Interior regulation place on the owner of the premises, its manager or its actual user: extinguishers serviced at least yearly, clear and marked escape routes, cleaning of flues and ducts, staff briefed on the rules and, usually, a fire safety instruction. Shortcomings can bring a fire service decision and, at worst, a ban on using the dining room.
This is an educational guide, not legal advice or an expert opinion. We quote provisions from texts published in the Journal of Laws (Dziennik Ustaw, Dz.U.) via api.sejm.gov.pl (opened 19.10.2026). The quotations are our own translations; the originals are Polish. Where a provision does not settle the matter directly, we write: interpretation. Figures marked "example" are our own calculation, not an authority's requirement. What we could not confirm in a legal act, we call "we did not establish". The regulation was recently amended, so check the current text before spending money.
Who is responsible for fire safety in the premises
The basis is art. 4(1) of the Fire Protection Act (ustawa o ochronie przeciwpozarowej). The owner of a building, facility or land must, among other things: meet the technical, building and installation requirements, equip the facility with fire protection devices and extinguishers, ensure their inspections, maintenance and repairs, ensure people's safety and ability to evacuate, brief employees on fire regulations and set procedures for a fire.
A restaurateur rarely owns the building, so paragraph 1a matters more. Responsibility for these duties, within the tasks entrusted, passes in whole or in part to the manager or user under a civil-law contract. Without such a contract, whoever actually controls the building or premises is responsible. For a tenant the conclusion is practical: clauses on extinguishers, inspections and the instruction carry real weight, and a silent lease does not lift the duties from whoever runs the venue. We cover drafting such a lease in our text on the lease agreement for a restaurant premises.
The costs fall on the obliged person too: art. 30 says the owner, manager or user bears in full the cost of acquiring and keeping in working order the equipment, devices and installations the regulations oblige them to have.
Fire protection tasks may be performed by people with the right qualifications (art. 4(2)). Persons not employed in fire protection units who perform tasks solely within art. 4(1) should have at least secondary education and the qualifications of a fire protection inspector or fire safety technician (para. 2b). Whether your venue needs an outside specialist, settle with an expert or the PSP county command; we found no sentence saying every small venue must hire an inspector (interpretation).
How the rules classify a restaurant
The Regulation of the Minister of Interior and Administration of 7 June 2010 on fire protection of buildings, other structures and land (Dz.U. 2010 no. 109 item 719, consolidated text Dz.U. 2023 item 822, amended in 2024 item 1716 and 2026 item 1276) has no separate chapter on catering. The scope of duties depends on the category of danger to people, set by the technical and building rules.
The regulation on technical conditions for buildings (warunki techniczne; consolidated text Dz.U. 2022 item 1225) counts among public-use buildings those intended, among other things, for "trade, catering, services". Note: according to ISAP (api.sejm.gov.pl, 19.10.2026) the 2002 regulation, together with this consolidated text, is marked as deemed repealed as of 21 September 2026, and we did not identify a successor. We give the ZL categories as worded in that text; how the authorities apply them today, check with an expert or the PSP county command. Two categories matter for a restaurant (§ 209(2)):
| Category | Content of § 209 | When it applies to a restaurant |
|---|---|---|
| ZL I | rooms for the simultaneous presence of more than 50 people who are not their permanent users, not intended primarily for people with limited mobility | a large dining room with over 50 guests at once (interpretation) |
| ZL III | public-use premises not classified as ZL I or ZL II | a smaller venue |
The category is set for a fire zone, not a business. A restaurant in a tenement building may be part of a larger zone or a zone of its own, as the building's documentation and the expert's opinion show. First determine the zone and category.
Extinguishers in a restaurant: how many, which type and where
Facilities are equipped with extinguishers meeting the Polish Standards (§ 32(1)). The type is matched to the fire classes that may occur: A, B, C, D and F, the last being fats and oils in kitchen appliances. In a restaurant the relevant ones are above all A (wood, paper, textiles), C (gas) and F (fryers, pans). The instruction and the expert will name the model.
How many: the 2 kg per 100 m² rule
Under § 32(3), every 100 m² of a fire zone that has no fixed extinguishing system and is classified ZL I, ZL II, ZL III or ZL V needs one unit of extinguishing agent of 2 kg (or 3 dm³). A restaurant falls under this rule.
Example: a fire zone of 240 m², no fixed extinguishing system.
| Step | Calculation (example) | Result |
|---|---|---|
| Units | 240 : 100 | 2.4 |
| Mass of agent | 2.4 × 2 kg | 4.8 kg |
| Rounding | the regulation is silent | up, to 3 units (interpretation) |
| Selection | 3 × 2 kg or 2 × 3 kg | 6 kg of agent |
| Kitchen | classes A, C, F | per the instruction and the expert |
The regulation does not say how to treat fractions or whether one larger extinguisher may replace several smaller ones. Such details are sometimes disputed in an inspection, so write the selection into the instruction and consult a specialist.
Where to hang extinguishers
§ 33 requires extinguishers in easily accessible, visible spots, in particular by room entrances and exits, away from mechanical damage and heat sources. Two figures you can check with a tape measure: from any place where a person may be, it is no more than 30 m to the nearest extinguisher, and access is at least 1 m wide.
So an extinguisher does not stand by the cooktop or behind crates of stock and guests' coats. This is a duty, not just good practice: § 4(1) point 18(a) prohibits restricting access to extinguishers, and art. 82 § 1 point 10 of the Code of Petty Offences (kodeks wykroczen) provides liability for it.
Extinguisher inspections: how often and who does them
§ 3(2) provides that fire protection devices and portable and mobile extinguishers "should undergo technical inspections and maintenance, in line with the rules and in the manner set out in the Polish Standards (...), in the technical and operating documentation and in the operating instructions drawn up by their manufacturers". Frequency is set by para. 3: inspections and maintenance "at intervals set by the manufacturer, but not less often than once a year".
It follows that:
- The lower limit is once a year, but if the manufacturer requires more frequent servicing, the shorter period applies.
- The scope of work is left to the Polish Standards and the manufacturer's documentation. We give no standard numbers because the regulation itself has none.
- The regulation does not say who must carry out the inspection. In practice service companies do; whether a company has the required authorisations, check in the contract and documentation (we did not establish a universal register of such companies in the provisions analysed).
Keeping equipment in working order is a separate duty: § 4(2) point 1 requires keeping fire protection devices and extinguishers in full technical and functional condition. An extinguisher with an overdue inspection, or an empty one, does not meet this even if it hangs on the wall. Failure is punished by art. 82 § 2 point 3 of the Code of Petty Offences.
The fire safety instruction: when it is required
§ 6(1) obliges owners, managers or users of facilities (or parts forming separate fire zones) intended for public use, collective residence, production, storage and livestock functions to provide and implement a fire safety instruction (instrukcja bezpieczenstwa pozarowego). Because catering counts as public use in the technical and building rules, a restaurant is as a rule covered (interpretation).
The exception: when no instruction is needed
§ 6(8) releases a facility from the instruction when two conditions are both met: there is no explosion hazard zone, and the gross volume of the building, or of the part forming a separate fire zone, does not exceed 1000 m³.
Example: a 150 m² venue 4 m high has 600 m³ gross volume, so with no explosion hazard zone it is below the threshold. A venue on two floors of 200 m² each, 3.5 m high, has about 1400 m³ and exceeds it. What counts is the gross volume of the building or separate fire zone, not the dining room alone, so take the data from documentation, not your own measurement. Whether a kitchen with a gas installation has an explosion hazard zone is judged by the designer or expert.
What the instruction contains
§ 6(1) lists the content. In short:
- fire protection conditions resulting from the purpose and manner of use of the facility,
- fire protection devices and extinguishers installed, and how they are inspected and maintained,
- how to act in a fire or other danger,
- safeguarding of fire-hazardous work (for example welding during a renovation),
- conditions and organisation of evacuation and practical ways of checking it,
- how users and employees are briefed on the rules and the instruction,
- fire protection tasks for permanent users,
- plans of the facility with graphic data (zones, exits, location of extinguishers and gas valves),
- who drew up the instruction.
Deadlines: the instruction is updated at least once every 2 years and after changes in use that affect protection conditions (§ 6(7)), and kept where rescue crews can reach it (para. 9). We did not establish that the PSP approves the instruction; the regulation requires it to be drawn up and implemented. For facilities under § 28(1), the protection conditions and plans go to the PSP county commander (§ 6(2)).
The fire procedure and emergency numbers
A separate, simpler duty comes from § 4(2) point 3: a fire procedure with a list of emergency numbers must hang in visible places. It applies to all buildings except single-family houses, so also to a restaurant exempt from the full instruction. Its absence is punished by art. 82 § 2 point 4 of the Code of Petty Offences.
The fire alarm system
§ 28(1) point 4 requires a fire alarm system in buildings with more than 300 seats for catering. Most venues stay below this, but food halls may exceed it. Whether the building or just your unit counts, settle with documentation and the expert (interpretation: the provision speaks of buildings).
Escape routes and signage
§ 15 requires suitable evacuation conditions from every place intended for people to stay: among other things a sufficient number and width of exits, length and width of passages, and emergency lighting. The dimensions come from the technical and building rules.
Day to day, watch the prohibitions in § 4(1):
- locking evacuation doors so they cannot be used immediately (point 14),
- storing combustible materials on escape routes and reducing their width (point 11),
- decor that reduces the dimensions of an escape route (point 16),
- restricting access to escape exits, switches and distribution boards and the main valve of the gas installation (point 18(e) and (f)).
Signage
§ 4(2) point 4 requires signs complying with the Polish Standards marking, among other things, escape routes and exits, places of extinguishers and fire protection devices, and the main gas valves. In a restaurant: signs by exits and extinguishers and a marked gas valve.
The 2026 regulation (Dz.U. 2026 item 1276, in force from 30 September 2026) added marking of shelter points under art. 84a of the Act on the Protection of the Population and Civil Defence, per annex 1a; points already identified must be marked without delay, no later than 31 December 2026. This concerns shelter points, not every venue. We did not establish whether yours is one; the authorities decide.
Practical evacuation check
§ 17(1) requires the owner or manager of a facility for more than 50 permanent users (other than ZL IV) to check evacuation in practice at least once every 2 years, notifying the PSP county commander at least a week ahead (para. 4). Example: a restaurant employing 14 people does not have 50 permanent users, because guests do not count towards that figure (interpretation), so the duty does not arise. The instruction, where required, still describes evacuation conditions and ways of checking them.
The extractor hood, ventilation ducts and cleaning of flues
On this topic guides often say more than the provision does, so let us separate facts from interpretation.
§ 34(1) concerns facilities where solid, liquid or gaseous fuel is burned. Deposits are removed from flues and exhaust ducts: from the furnaces of collective catering and catering services "at least once a month, unless local regulations provide otherwise"; from solid-fuel furnaces not listed above, at least every 3 months; from liquid- and gas-fuel furnaces, at least every 6 months.
§ 34(2): in those facilities, deposits are removed from ventilation ducts "at least once a year, unless a higher frequency follows from the conditions of use". People with chimney-sweep qualifications do the work (para. 3).
What is not in this provision? The words "hood" and "grease". The regulation gives no cleaning interval for the extractor hood and exhaust duct of a commercial kitchen. Hence:
- Fact: flues and exhaust ducts from catering furnaces are cleaned at least monthly; ventilation ducts in facilities with combustion at least yearly, more often where conditions of use require.
- Interpretation: a gas kitchen is a facility with gas combustion, so the annual limit may also apply to its ventilation. Whether the duct above a fryer is a "ventilation duct" under para. 2, and how often to clean it because of grease, is decided by analysing the installation. The phrase "conditions of use" suggests that with heavy frying once a year is sometimes too rare.
- We did not establish: any other interval (for example quarterly) for hoods in the regulation's text. If you see such a figure in a guide, check whether it rests on the provision or on a recommendation of the manufacturer, insurer or a standard.
The hood's documentation helps: § 4(1) point 2 prohibits using faulty installations and devices, or using them contrary to the manufacturer's conditions. The manufacturer's recommendations on cleaning grease filters are therefore in practice part of the duty, even though the regulation lacks them. In art. 82 § 2 point 7 the Code of Petty Offences punishes failure to ensure removal of deposits from flues and exhaust ducts; that concerns para. 1 of § 34, not ventilation.
Example of organisation: you order the monthly inspection of flues and exhaust ducts from a person with chimney-sweep qualifications, file the report in the fire safety binder, and agree with the contractor a ventilation schedule no less frequent than yearly.
Carbon monoxide detector
The 2024 regulation added § 28a(3): at least one standalone carbon monoxide detector in a room with fuel combustion that is part of a commercial unit intended for people to stay in a ZL zone. Para. 4 excludes appliances with a sealed combustion chamber and gas appliances for preparing meals. A gas cooker is therefore excluded, but a boiler room with an open chamber may trigger the requirement (interpretation). For existing commercial units the date of application was 30 June 2026 (§ 2(4) of the 2024 regulation), so it has passed.
Combustible materials in the kitchen and the dining room
The regulation contains prohibitions that address typical venue situations directly (§ 4(1)):
- point 2: using faulty installations, or using them contrary to the manufacturer's conditions,
- point 8: combustible materials and combustible decor closer than 0.5 m to appliances and installations that heat above 373.15 K (100 °C), that is, an oven, grill or heater; cardboard and decorations must be moved away,
- point 13: full, partly full and empty cylinders for flammable gases in non-habitable attics and lofts and in cellars.
Training employees: what the rules say
Art. 4(1) point 6 of the Act requires employees to be briefed on fire regulations. The Labour Code adds its own: art. 237⁴ § 1 requires employees to be briefed on occupational health and safety rules, and § 3 provides for confirmation on paper or electronically.
Art. 209¹ § 1 of the Labour Code requires the employer to provide the means to fight fires and evacuate employees, designate employees for fire-fighting and evacuation, and ensure communication with external services, including in fire protection. Their number, training and equipment must match the type and level of hazards. Example: on every shift a named person leads the evacuation of guests, and a deputy knows where the extinguisher is and how to close the gas valve.
What is missing here? We did not establish a fixed interval for fire safety training for restaurants in these acts. The rhythm of occupational health and safety training follows from a separate regulation we do not analyse. If an instruction is required, § 6(1) point 6 tells you to describe in it how employees are briefed, and then it sets the training rhythm in your venue.
Inspection by the State Fire Service (PSP)
Under art. 23(1) of the State Fire Service Act (ustawa o Panstwowej Strazy Pozarnej), the PSP carries out inspection and reconnaissance activities to identify hazards, supervise compliance with fire regulations and prepare rescue operations. The grounds are listed in para. 2 (among others, the annual plan, an order from a court or prosecutor, notification of a facility requiring a PSP opinion, notice from the mayor).
What the inspected party can expect:
- the authorisation is, as a rule, delivered at least 7 days before the start (3 days in matters of PSP opinions or positions); where life is threatened or fire is an immediate danger it may be delivered when the activities begin (para. 7),
- inspectors show their service ID or identity document (para. 9),
- the inspected party gives information (and agrees to photographic documentation), allows access to facilities and devices, and ensures access to documentation and copies (para. 10),
- the findings go into a report both sides sign; the inspected party may raise objections (paras. 13-14),
- when a business is inspected, chapter 5 of the Entrepreneurs' Law (Prawo przedsiebiorcow) applies (art. 23a).
What the commander may order
Under art. 26(1) of the State Fire Service Act, the county (city) commander may by decision order the removal of shortcomings within a set time or, if they may endanger life or cause an immediate danger of fire, halt works, prohibit the use of devices and of rooms or facilities. Decisions to halt and to prohibit are immediately enforceable (para. 2), and the appeal body is the voivodeship commander (art. 27). For a restaurant this means a break in serving guests until the shortcoming is removed. Firefighters may also impose a penalty ticket (art. 23(6)).
Penalties in the Code of Petty Offences
Art. 82 of the Code of Petty Offences (consolidated text Dz.U. 2025 item 734) provides for a venue mainly:
- § 1: acts that may cause a fire or hinder evacuation, among others using faulty installations (point 3), storing combustible materials on escape routes (point 7), failing to observe safety rules when using or storing fire-hazardous materials, including liquefied gas in cylinders (point 5), restricting access to extinguishers, distribution boards, gas valves and escape exits (point 10),
- § 2: failure of the person obliged to provide protection to meet duties: evacuation conditions (point 1), extinguishers (point 2), their working order (point 3), posting the instruction with phone numbers (point 4), safety signs (point 5), removal of deposits from flues and exhaust ducts (point 7),
and the sanction is detention, a fine or a reprimand. Art. 82a § 1 also punishes failing to notify without delay people in the danger zone and the services in a fire. Art. 82a § 3 punishes preventing or obstructing inspection activities (detention, restriction of liberty or a fine).
The fine: art. 24 § 1 provides from 20 to 5000 zloty, unless a statute provides otherwise. The raised ceiling of 30,000 zloty in art. 24 § 1a applies to the petty offences listed there by number, and art. 82 is not among them, so on our reading the general range applies (interpretation). Note: art. 82 § 2 does not expressly name the lack of a full instruction under § 6; whether it falls under another point depends on the case. The consequences of a fire itself (danger to life, damage) are a separate liability we do not analyse.
Restaurant owner's checklist
- I know the ZL category (I or III) and the fire zone of my premises.
- There are as many extinguishers as the 2 kg per 100 m² rule gives, and the type fits classes A, C and F.
- From every spot it is no more than 30 m to an extinguisher, and access is at least 1 m wide.
- Every extinguisher has an inspection no older than a year (or shorter if the manufacturer requires).
- Escape exits are clear, not locked with a key and marked.
- The distribution board and main gas valve are accessible and marked.
- I know whether I must have a fire safety instruction and, if so, that it is up to date.
- A fire procedure with emergency numbers hangs in a visible place.
- Flues and exhaust ducts are cleaned monthly, ventilation at least yearly.
- Employees have signed that they know the rules, and each shift has people responsible for evacuation.
- The lease says who is responsible for inspections and the instruction.
Where AURA fits in all this
AURA is in preparation: it does not issue inspection reports, does not replace the fire safety instruction and does not assess whether the premises comply with the rules. How a screen with the venue's fixed costs could look is shown by the demo version on sample data: the demo dashboard. It is a demonstration, not a feature you can buy. On fire protection, rely on the Journal of Laws and an expert's opinion.
Frequently asked questions
How often must extinguishers be inspected in a restaurant?
Under § 3(3) of the Ministry of Interior regulation, inspections and maintenance are carried out at intervals set by the manufacturer, but not less often than once a year. If the manufacturer specifies a shorter period, that applies.
Does a small restaurant need a fire safety instruction?
As a rule yes, as a public-use facility. The § 6(8) exception works only where there is no explosion hazard zone and the gross volume of the building or separate fire zone does not exceed 1000 m³. Check the data in the building's documentation.
How many extinguishers must a catering venue have?
For ZL I, II, III and V zones without a fixed extinguishing system, one unit of 2 kg (or 3 dm³) of agent per 100 m² of fire zone (§ 32(3)). The type must match the fire classes; in the kitchen, among others, class F.
How often are the hood and ventilation ducts cleaned in a restaurant?
The regulation does not mention the hood directly. Ventilation ducts in facilities with combustion are cleaned at least yearly unless a higher frequency follows from the conditions of use, and flues and exhaust ducts from catering furnaces at least monthly (§ 34). We did not establish a separate interval for hoods.
What are the penalties for missing extinguishers or a blocked escape exit?
Art. 82 of the Code of Petty Offences provides detention, a fine or a reprimand, and the fine is as a rule from 20 to 5000 zloty (art. 24 § 1). The PSP commander may in addition ban the use of rooms by an immediately enforceable decision.
Who is responsible for fire safety in a rented premises?
Under art. 4(1a) of the Act, the manager or user takes over responsibility under a civil-law contract; without a contract, whoever actually controls the premises is responsible. Write the scope into the lease.
Do I have to train employees in fire regulations?
The Act (art. 4(1) point 6) requires employees to be briefed on fire regulations, and art. 209¹ of the Labour Code requires designating employees for fire-fighting and evacuation. We did not establish a fixed interval of fire safety training for restaurants.
What does a fire service inspection look like?
Firefighters with an authorisation, as a rule delivered 7 days before the date, check the facility and documents, and the findings go into a report to which objections can be raised (art. 23 of the State Fire Service Act). After the inspection the commander may order the removal of shortcomings within a set time.
Sources
- Fire Protection Act (ustawa o ochronie przeciwpozarowej), consolidated text Dz.U. 2025 item 188 (art. 4, 30): https://api.sejm.gov.pl/eli/acts/DU/2025/188/text.pdf (opened 19.10.2026).
- Ministry of Interior and Administration regulation on fire protection of buildings, other structures and land, consolidated text Dz.U. 2023 item 822 (§ 3, 4, 6, 15, 17, 28, 32-34): https://api.sejm.gov.pl/eli/acts/DU/2023/822/text.pdf (opened 19.10.2026).
- Amending regulation, Dz.U. 2024 item 1716 (detectors, § 28a): https://api.sejm.gov.pl/eli/acts/DU/2024/1716/text.pdf (opened 19.10.2026).
- Amending regulation, Dz.U. 2026 item 1276 (shelter points): https://api.sejm.gov.pl/eli/acts/DU/2026/1276/text.pdf (opened 19.10.2026).
- State Fire Service Act (ustawa o Panstwowej Strazy Pozarnej), consolidated text Dz.U. 2025 item 1312 (art. 23, 23a, 26, 27): https://api.sejm.gov.pl/eli/acts/DU/2025/1312/text.pdf (opened 19.10.2026).
- Code of Petty Offences (kodeks wykroczen), consolidated text Dz.U. 2025 item 734 (art. 24, 82, 82a): https://api.sejm.gov.pl/eli/acts/DU/2025/734/text.pdf (opened 19.10.2026).
- Labour Code (kodeks pracy), consolidated text Dz.U. 2026 item 1245 (art. 209¹, 237⁴): https://api.sejm.gov.pl/eli/acts/DU/2026/1245/text.pdf (opened 19.10.2026).
- Regulation on technical conditions for buildings (warunki techniczne), consolidated text Dz.U. 2022 item 1225 (§ 3 point 6, § 209; status "deemed repealed" from 21.09.2026 per ISAP): https://api.sejm.gov.pl/eli/acts/DU/2022/1225/text.pdf (opened 19.10.2026).